Category:Residential Energy Storage Systems, solar battery storage, solar panel battery storage, solar battery for commercial, LFP battery, High Voltage battery,BYD battery
●IP65 protection, aluminum housing, built-in lightning protection, high-precision leakage protection
●It is more economical to support multiple operating modes,
●Can be as a UPS for the important loads when power off,
●Support intelligent EMS management function,
●Support on/off-grid automatic switching function to ensure uninterrupted power when important loads are off-grid
●Integrate PV and storage system modem,
●Support full power discharge, automatic management of battery charge and discharge,
●Wide PV and battery voltage input range,
●Support multiple parallel connections
| Datasheet | SNE30K-G3 | SNE40K-G3 | SNE50K-G3 | SNE60K-G3 |
| DC Input | ||||
| Max. power(kW) | 36KW | 48KW | 60KW | 72KW |
| Max. DC voltage(V) | 1000V | |||
| MPPT voltage range(V) | 180V-900V/630V | |||
| MPPT operating voltage range at rated power(d.c.V) | 300V-900V | 400V-900V | 400V-900V | 450V-900V |
| MPPT tracker/strings | 2/2/2 | 2/2/2 | 2/2/2/2 | 2/2/2/2 |
| Max.input current of single MPPT(A) | 36A*3 | 36A*3 | 36A*4 | 36A*4 |
| Short-circuit current of PV input(A) | 42A/42A/42A | 42A/42A/42A | 42A/42A/42A/42A | 42A/42A/42A/42A |
| AC Output | ||||
| Rated output power(kW) | 30KW | 40KW | 50KW | 60KW |
| Max. Apparent AC power(KVA) | 30KVA | 40KVA | 50KVA | 60KVA |
| Max. output current(A) | 45A | 60A | 75A | 87A |
| Grid voltage/range(V) | 400V, 3L+N+PE | |||
| Frequency (Hz) | 50 /60Hz | |||
| PF | 1(0.8lagging-0.8leading) | |||
| THDI | <3% | |||
| Battery | ||||
| Battery voltage range(V) | 220V~800V | |||
| Max. input/output voltage(V) | 800V | |||
| Rated charge/discharge current(A) | 100A | 100A | 100A | 100A |
| Max. input/output power(KW) | 30KW | 40KW | 50KW | 60KW |
| Battery type | lithium /Lead-acid | |||
| Communication interface | CAN/RS485 | |||
| EPS Output | ||||
| Rated output power(kW) | 30KW | 40KW | 50KW | 60KW |
| Max. Apparent AC power(KVA) | 30KVA | 40KVA | 50KVA | 60KVA |
| Max. single-phase apparent output power(KVA) | 10KVA | 13KVA | 17KVA | 20KVA |
| Rated output voltage(V) | 400V, 3L+N+PE | |||
| Rated output current(A) | 45A | 60A | 75A | 87A |
| Rated frequency (Hz) | 50Hz /60Hz | |||
| Automatic switching time (ms) | <10ms | |||
| THDU | <3% | |||
| Overload capacity | 110%, 30S/120%, 10S/150%, 0.02S | |||
| Protection parameters | ||||
| AC over-current protection | Yes | |||
| Ground fault detection protection | Yes | |||
| Power grid monitoring protection | Yes | |||
| Residual current detection protection | Yes | |||
| General Data | ||||
| Euro Efficiency | >98.2% | |||
| Protection class | IP54 | |||
| Noise Emission (Typical) | <40dB | |||
| Operation Temperature | -25~+60℃ | |||
| Cooling | Intelligent Fan | |||
| Relative Humidity | 5 ~90% (non-condensing) | |||
| Altitude | 4000m(>2,000 Derating) | |||
| Dimensions (W/D/H) mm | 800*600*280mm | |||
| Weight(kg | 50KG | |||
| Inverter Topology | transformerless | |||
| Self-Consumption | <1W | |||
| Display and communication | ||||
| Display | LCD | |||